LCD card three-phase meter RS485 Modbus meter
Measure all three-phase electrical parameters (three-phase current, three-phase voltage, three-phase active power, combined active power, three-phase
Product details
Multi functional network power meter
Measure all three-phase electrical parameters (three-phase current, three-phase voltage, three-phase active power, combined active power, three-phase reactive power, combined reactive power, three-phase apparent power, combined apparent power, three-phase power factor, combined power factor, frequency), active energy, reactive energy, etc.
Standard RS485 interface, international standard Modbus rtu protocol, providing upper computer testing software, and engineering example programs for Kingview software.
Optional 4-channel switch input, 4-channel switch output, and 2-channel analog output module.
User Manual for Multi functional Power Meter
Debugging tool software manual download: http://pan.baidu.com/s/1kTww5O7
Brief introduction
This series of products is a multifunctional intelligent instrument with programmable measurement, display, digital communication, and power pulse output. It can complete power measurement, power metering, data display, acquisition, and transmission, and can be widely used in substation automation, distribution automation, intelligent construction, internal power measurement, management, and assessment of enterprises. The measurement accuracy is 0.5 level, realizing LCD on-site display and remote RS-485 digital interface communication, using MODBUS-RTU communication protocol.
3、 Installation and wiring
3.1 Instrument dimensions
3.2 Installation Method
(1) Open holes of varying sizes in the fixed distribution cabinet;
(2) Remove the instrument panel, loosen the screws, and remove the fixed bracket;
(3) The instrument is inserted into the installation hole from the front;
(4) Insert the instrument mounting bracket and tighten the screws to secure the instrument.
External dimensions:
This model of instrument has 4 different shapes, with a panel size of 96X96120X120. Two shapes can be equipped with functional modules such as switch input, switch output, and transmission output.
Panel size: 72X72mm, hole size: 68X68mm, depth: 90mm
Panel size: 80X80mm, hole size: 76X76mm, depth: 90mm
Panel size: 96X96mm, opening size: 91X91mm, depth: 80mm
Panel size: 120X120mm, opening size: 111X111mm, depth: 80mm
RS485 communication module:
RS458 supports standard Modbus rtu protocol commands: 01H, 02H, 03H, 04H, 05H, 0FH, 10H. Baud rate: 240048009600. Data format: 8-bit data bits, no checksum, 1-bit stop bit; 8-bit data bit, odd parity, 1-bit stop bit; 8-bit data bit, even check, 1-bit stop bit; 8 data bits, no checksum, 2 stop bits. The communication address, baud rate, and data format can be set through the instrument menu. All measured electrical parameters and parameter settings can be read out through the RS485 interface and can be connected to various PLCs, HMI, Configure software networking.
Relay output, switch input, transmission module output, additional fees depending on the number of modules!
Relay output module:
Up to 4 relays can be selected, which can operate in alarm or remote control mode. When working in an alarm state, the relay is associated with one of the measured electrical parameters, and if it is lower or higher than the set alarm value, the relay will act; When working in remote control mode, the action of the relay is controlled by Modbus rtu commands 05H, 0FH, 10H through the RS485 interface.
Switch input module:
Up to 6 switch inputs can be selected, using dry node resistance switch signal input method. The instrument is equipped with a+15V working power supply inside, which does not require external power supply. It can be used to monitor functions such as fault alarm nodes, opening and closing status, handcart position, capacitor compensation cabinet capacitor input status, etc. The status information can be remotely transmitted to the intelligent monitoring system through the communication interface. With the remote control/alarm relay function, automatic opening and closing can be easily achieved. The status of switch input monitoring can be set as the condition for relay output action, achieving functions such as locking and interlocking.
Transmission output module:
Up to 2 analog transmission output functions are provided, each of which can select any one of the 26 electrical parameters as the transmission output item. Through the instrument's own transmission output function, the analog transmission output function of electrical parameters (0-20mA, 4-20mA, 0-10-20mA, or 4-12-20mA) can be achieved, and the corresponding quantity relationship can be set arbitrarily.
3.3 Terminal Wiring Diagram
(Note 1: The wiring method is the same for different sizes)
(Note 2: The asterisk on the current line indicates the incoming line, and the incoming and outgoing lines are reversed. The electrical energy is measured to be in reverse phase.)
4、 Programming operation
4.1 Entering and Exiting Programming State
Enter programming mode:
Press and hold the "SET" key for 1 second while measuring the display status to enter the password authentication page. Use the "?", "▲", and "▼" keys to enter the password (default user password is 1111), and then press the "SET" key to enter the programming status page. Note: If you enter the password and press the "SET" key to exit the measurement display state, it means that the password entered is incorrect.
Exit programming state:
In programming mode, hold down the "SET" button for 2 seconds to exit the programming mode. The user will be prompted to choose whether to save the setting values. "Yes" will save the setting values, and "No" will not save them. Press the "SET" key to save, press other keys not to save.
4.2 Use of keys in programming operations
Function key SET: Confirm the setting value, enter the next setting or exit the setting.
Position selection key?: Cycle to select the digital tube to be set, and the selected tube will flash.
Add key ▲: Change the value of the flashing digital tube (the digital tube value cycles from 0 to 9).
Reduce key ▼: Change the value of the flashing digital display (the digital display value cycles from 9 to 0).
5.3 Parameter Setting Instructions

Serial Number

Description of serial number content

display

range

Enter menu password

CodE

0~9999

Description: Enter the password to enter the menu. Only with the correct password can you enter the menu. The factory default value is 1111

1

Connection

NEt

3P3L, 3P4L

Instructions: 3P3L three-phase three wire connection, 3P4L three-phase four wire connection

2

Voltage multiplier

Pt

1~9999

Explanation: This setting is for the multiplier of the PT used in the line, with a factory preset value of 1. If the PT type used in the line is 10kV/100V, the setting value for this item is 100

3

Current rate

Ct

1~9999

Explanation: This setting is for the magnification of the CT used in the circuit, with a factory preset value of 1. If the CT type used in the circuit is 600A/5A, the setting value for this item is 120

4

Display mode

diSP

0~99

Explanation: 0 is a fixed display mode, manually switch display items; Set the page to automatic switching from 1 to 99, with the value set as the interval time for display in seconds

5

mail address

Addr

1~247

Explanation: The instrument address is used to identify the local machine during multi machine communication

6

Baud rate

bAUd

2400, 4800, 9600, 19200, 38400

Description: Used to set the baud rate for RS485 communication, with a factory default value of 9600

7

Communication data format

dAtA

n.8.1、o.8.1、e.8.1、n.8.2

Explanation: n.8.1 has 8 data bits and 1 stop bit without checksum, o.8.1 odd checksum has 8 data bits and 1 stop bit, e.8.1 even checksum has 8 data bits and 1 stop bit, n.8.2 has 8 data bits and 2 stop bits without checksum

8

Electric energy clearing 0

Eclr

yes、no

Explanation: Yes, the energy data is cleared to 0, and no, the energy data remains unchanged

9

Save parameter modification value selection

SAVE

yes、no

Explanation: Yes saves the modified parameter values, no keeps the previous parameter values unchanged

10

Menu entry password

Code

0~9999

Description: Set the password to enter the menu, with a preset value of 1111

Six (detailed explanation, subject to the random instruction manual on the registration form)