XY-DM422Manual for Intelligent Dimming Control Module
Chapter OnePRODUCT FUNCTION
l twoRS485Communication orRS485+Ethernet communication;
l Supported Standardsmodbus RTU(TCP)Agreement.
l Human computer interaction, LCD display, automatic mode, linkage mode, manual mode
l 2road0-10VOutput,2roadPWMModulation of thyristor output;
l 4Road switch input, can be linked with output;
l 1Analog input for environmental temperature detection, light detection, etc;
l Supporting baud rate:2400,4800,9600,19200,38400
Chapter 2Product Selection
PRODUCT MODEL |
RS485+RS485 |
RS485+TCP |
XY-DM422-S |
● |
|
XY-DM422-NS |
|
● |
Chapter IIIParameters
parameter |
describe |
communication interface |
RS485Ethernet |
rated voltage |
DC9-30VperhapsAC220V |
RUN |
Flashing normally once per second |
Communication instructions |
communicationLEDOne indicator light. |
temperature range |
-10℃ to65℃ |
size |
108(L)X 88(W)X 65(H) |
Installation method |
35mmCard rail installation |
Default communication format |
9600, n,8,1 |
Baud rate |
2400,4800,9600,19200,38400 |
Software support |
Supporting configuration software and control software; Support various configuration software and human-machine interfaces; Support, Kingview, Power ControlLabviewclass |
weight |
300g |
Chapter FourInterface Description
1. Working power supply: Positive power supply 12V, Power Ground:GND(AC220VFor optional selection, byLIN1/L、NIN1/NEnd to end power supply
2. communicationPort wiring method
l RS485Ainterface:Upload communication port
Communication lineD+(A);
Communication lineD-(B);
l Ethernet: (optional)
l RS485Binterface:
Communication lineD+(A);
Communication lineD-(B);
l Photosensitive interface
S+: Light sensitive signal+
S-: Light sensitive signal-
l Switch input interface
IN1(DC1)DC voltage output1Trigger end
IN2(DC2)DC voltage output2Trigger end
IN3(AC1)AC voltage output1Trigger end
IN4(AC2)DC voltage output2Trigger end
l DCVoltage output port:
GND:DCVoltage output common terminal;
VOUT1:DCVoltage output terminal 1
VOUT2:DCVoltage output terminal 2
l ACOutput port (thyristor dimming)
LIN1/L:The first thyristor AC voltage inputLEnd(AC220Vpower supplyLEnd)
NIN1/N:The first thyristor AC voltage inputNEnd(AC220Vpower supplyNEnd)
NOUT1:The first thyristor controlled outputNend
LOUT1:The first thyristor controlled outputLend
LIN2:Second channel thyristor AC voltage inputLend
NIN2:Second channel thyristor AC voltage inputNend
NOUT2:Second thyristor controlled outputNend
LOUT2:Second thyristor controlled outputLend
Chapter VModbusRegister Description
Register address |
Support function code |
describe |
|
0x0000 |
0x03,0x06 |
|
|
0x0001 |
0x03,0x06 |
|
|
0x0002 |
0x03,0x06 |
|
|
0x0003 |
0x03,0x06 |
auxiliary word for ordinal numbers4Road dimming value(0-100)(220VAC output1) |
|
0x001F |
0x06 |
Simultaneously set dimming values for all channels |
|
0x0020 |
0x03,0x06 |
auxiliary word for ordinal numbers1Road dimming change cycle(0-99)(Unit)0.1S) |
|
0x0021 |
0x03,0x06 |
auxiliary word for ordinal numbers2Road dimming change cycle(0-99)(Unit)0.1S) |
|
0x0022 |
0x03,0x06 |
auxiliary word for ordinal numbers3Road dimming change cycle(0-99)(Unit)0.1S) |
|
0x0023 |
0x03,0x06 |
auxiliary word for ordinal numbers4Road dimming change cycle(0-99)(Unit)0.1S) |
|
0x003F |
0x06 |
Simultaneously set all channel change cycles |
|
0x0040 |
0x03,0x06 |
Working mode0Switching linkage, oneRegister settings) |
|
0x0041 |
0x03 |
Analog input value |
Chapter VIInstructions for use and setup
1. Interface Description
Main interface, displaying the current input/output status
DC voltage output setting page, on time (time from current state to fully open), off time (time from current state to fully closed)
2. Button Description
Long press on the main interface“
On the settings page, short press“
On the voltage output setting page or thyristor output setting page, you can press“
By“
3. Control instructions
When the module is set to register mode, throughModbusThe protocol writes the value of the corresponding channel register to adjust the brightness.
When the module is set to input linkage mode, it is switch input control
The switch input terminals, from right to left, areCOM,IN1,IN2,IN3,IN4
of whichCOMFor the public end,IN1,IN2For the voltage output control terminal,IN3,IN4Output control terminal for thyristor
equalIN1,IN2When the input is short circuited to the common terminal, the corresponding voltage output will control the output according to the set switching time0Change to10VOn the contrary, from10VChange to0V.
equalIN3,IN4When the input is short circuited to the public area terminal, the corresponding thyristor output control will control the light to change from off to the brightest according to the set switch time, and vice versa.