1、 Overview of blue widescreen paperless recorder:
The ARS6400R blue screen paperless recorder has a maximum of 12 analog input channels, 2 pulse input channels, 6 alarm output channels, 4 analog output channels, 4 PID control circuits, and 100mA distribution output. It also has 1 RS-232C communication interface, 1 isolated RS-485 communication interface, and 1 USB interface. The collected data is stored in RAM memory, which can display real-time data and recall historical data in various forms such as curves, engineering quantity data, and percentages. The data can also be transmitted remotely through RS-232C and RS-485 communication interfaces.
The ARS6400R blue screen paperless recorder integrates multiple functions such as display, processing, recording, and alarm, and can collect, store, and analyze important data in various industrial processes. It is mainly used in various industrial sites such as metallurgy, petroleum, chemical, building materials, papermaking, food, pharmaceuticals, heat treatment, water treatment, etc. It is a new generation paperless recorder that replaces traditional recorders.
2、 Blue screen paperless recorder product screen display:

3、 Technical specifications of widescreen blue paperless recorder product:
Number of channels
12 universal signal inputs.
display
7-inch blue screen 480 × 240 graphic dot matrix
Input Signal Type
Type II standard signal: (0~10) mA, (0~5) V.
Type III standard signal: (4~20) mA, (1~5) V.
9 types of thermocouples: B, E, J, K, S, T, WRe5-26, R, N.
Two types of thermal resistors: Pt100 and Cu50.
accuracy
0.02%
Input impedance
The standard voltage signal and (-10~10) V input are 1M Ω.
The standard current signal input is 250 Ω.
Other signal inputs are greater than 20M Ω.
quarantine
The isolation voltage between channels and ground is greater than 500VAC, fully isolated type, and the isolation voltage between channels is greater than 250VAC.
thermocouple
The internal resistance is not greater than 1000 Ω, and there are three processing methods for detecting broken couples: starting point, ending point, and holding.
thermal resistance
Pulse excitation, instantaneous current of 0.25mA, maximum lead resistance of 10 Ω, all three wires are the same.
power supply
AC power supply voltage: (100~240) VAC; Frequency: (47~63) Hz; Maximum power consumption: 30VA;
DC power supply voltage: 24VDC.
Fuse specifications
1.0A/250VAC, Slow melting type, no need to replace when in use.
Distribution specifications
30mA per channel, 24VDC.
ALARM IN
250VAC, 3A relay output.
analog output
Output signal type: (4~20) mA.
hardware watchdog
Integrate WATCHDOG chip to ensure long-term safe and reliable operation of the host.
Real Time Clock
Using hardware real-time clock, powered by lithium battery after power failure, with a maximum clock error of ± 1 minute/month.
Power failure protection
All data is stored in FLASH memory without the need for backup batteries, ensuring that all historical data and configuration parameters are not lost due to power failure.
communication interface
Two communication interfaces, RS-485 and RS-232C, are provided for users to choose from, but they cannot be used simultaneously. The RS-485 serial bus is isolated from the host
Communication protocol
Adopting R-Bus communication protocol, there are 5 selectable communication baud rates, namely 1200 bps, 9600 bps, 19200 bps, 57600 bps, and 115200 bps
sampling period
1 second, which means sampling each channel once per second
record
The recording interval is divided into 9 levels: 1 second, 2 seconds, 4 seconds, 10 seconds, 30 seconds, 1 minute, 10 minutes, 30 minutes, and 60 minutes. The length of the recording time is related to the recording interval and the number of channels.
size
Dimensions: 180mm * 144mm * 104mm, hole size: 138mm * 138mm
4、 Recorder selection table:

Note: A. 12 analog inputs, the first 8 universal inputs, and the last 4 cannot input PT100 signals
B、 If there is an analog output, the maximum number of analog inputs can only be 8
5、 Installation dimensions of paperless recorder: