Overview
DS862The three-phase three wire active energy meter is used to measure the rated frequency50HzInductive instruments for active or reactive energy consumption in three-phase AC power grids. The technical performance of the three-phase power meter fully complies with the requirementsGB/T17215.311-2008《AC measuring equipment Special requirements 第11Part: Electromechanical active energy meter(0.5、1and2level)》National standards andIEC521national standard.
Main functional features
■The voltage and current iron cores are both made of high-quality silicon steel sheets and formed by high-speed punching and riveting
■The instrument bearing can be selected from three structures: double gemstone, magnetic push, or magnetic suspension
■archAluminum alloy die-casting integral bracket ensures stable and reliable magnetic circuit
■Optional rubberwoodPCTheABSPlastic, glass, aluminum, etc5Seed shell
Main technical parameters
|
project |
Technical Specifications |
|
accuracy class |
2level |
|
Voltage specifications |
3×100V、3×380V |
|
Current specifications |
3×1.5(6)A、3×3 (6)A、3×5(20)A、3×10(40)A、3×15(60)A、3×20(80)A、3×30(100)A |
|
Reference frequency |
50Hz |
|
Working voltage range |
Specify the working voltage range:0.9Un~1.1Un |
|
Expand the working voltage range:0.8Un~1.2Un |
|
|
Working temperature range |
Specify the working temperature range:-25℃~+55℃ |
|
Extreme operating temperature range:-40℃~+70℃ |
|
|
Storage and transportation limit temperature range:-40℃~+70℃ |
|
|
power consumption |
≤1.2W |
|
Overall dimensions |
≤40A 273mm×172mm×124mm(Subject to physical object) ≥60A 279mm×172mm×124mm(Subject to physical object) |
Appearance and installation dimensions
wiring diagram