Product features and uses:
Suitable for industrial and mining enterprises such as petroleum, chemical, power generation, metallurgy, etc., as signal transmission lines for electrical instruments and automation control systems in harsh environments of high temperature, low temperature, acid, alkali, oil, water, and corrosive gases
| Usage characteristics: |
| Working temperature: KFF-200, KFP1F-200, KFP1F22, KFP1F22-260 models not exceeding 200 ℃ |
| Rated voltage Uo/U: 450/750V and below |
Minimum ambient temperature: Fixed installation -60 ℃ Non fixed laying -20 ℃ |
Minimum bending radius: KFF type should not be less than 10 times the outer diameter of the cable; KFF22,KFP1F,KFP1F22, It should not be less than 12 times the outer diameter of the cable. |
| Main technical indicators: |
| project |
technical indicators |
guide body straight flow electricity block |
|
0.2 |
0.35 |
0.5 |
0.75 |
1.0 |
1.5 |
2.5 |
4.0 |
6.0 |
| No tin plating |
tin-plating |
No tin plating |
tin-plating |
No tin plating |
tin-plating |
No tin plating |
tin-plating |
No tin plating |
tin-plating |
No tin plating |
tin-plating |
No tin plating |
tin-plating |
No tin plating |
tin-plating |
No tin plating |
tin-plating |
| Types of conductors |
Class AB |
92.3 |
94 |
55.8 |
57.5 |
36.0 |
36.7 |
24.5 |
24.8 |
18.1 |
18.2 |
12.1 |
12.2 |
7.41 |
7.56 |
4.61 |
4.70 |
3.08 |
3.11 |
| Class R |
/ |
/ |
/ |
/ |
39.0 |
40.0 |
26.0 |
26.7 |
19.5 |
20.0 |
13.3 |
13.7 |
7.98 |
8.21 |
4.95 |
5.09 |
3.03 |
3.39 |
| Test voltage |
Rated voltage 450/750V Test voltage 2500V/1min Rated voltage 300/500V and below Test voltage 2000V/1min |
| insulation resistance |
20℃时≥500 MΩ·km |
|
| Model and Name |
| model |
name |
Remarks |
| KFF-200 |
F46 insulated and sheathed high-temperature resistant cable |
Long term working temperature of 20 ℃ |
| KFP1F-200 |
F46 insulated and sheathed shielded high-temperature resistant cable |
| KFF22-200 |
F46 insulated and sheathed steel tape armored high-temperature resistant cable |
| KFP1F22-200 |
F46 insulated and sheathed steel tape armored shielded high-temperature resistant cable |
|
| Model Description |
| project |
code name |
Explanation |
| Series code |
K |
control cable |
| insulating material |
F |
The maximum working temperature of perfluoroethylene propylene (F46) is 200 ℃ |
| Fusible polytetrafluoroethylene (PFA) with a maximum working temperature of 260 ℃ |
| Shielding material |
/ P1 |
No shielding can be omitted tinned copper wire |
| sheath material |
F |
The maximum working temperature of perfluoroethylene propylene (F46) is 200 ℃ Fusible polytetrafluoroethylene (PFA) with a maximum working temperature of 260 ℃ |
| Armored material |
22
32 |
Steel tape armoring Fine steel wire armor |
| Conductor coating |
/ Y |
Tin plating omission silver-plated |
| Heat resistance level |
200
260 |
Maximum working temperature of 200 ℃ Maximum working temperature 260 ℃ |
| Specifications |
|
Fill in the number of cores x conductor cross-section (N x S) N:2 3 4 5 7 8 10 12 14 16 19 24 27 30 37 44 48 52 S:0.2 0.35 0.5 1.75 1.0 1.5 2.5 4.0 6.0(mm2)℃ |
Types of conductors (Fill in parentheses) |
A B R |
Single stranded conductor Seven stranded conductor Multi strand soft conductor |
|
|
|
|