function |
Testing of equipotential bonding resistance between metal components, low value resistance testing, DC resistance testing, resistance testing of connecting conductors between ground grid electrodes, contact resistance and riveting resistance testing; Wire length testing, etc |
|
|
power supply |
DC 7.4V 2.6Ah rechargeable lithium battery, fully charged to approximately 8.4V |
|
|
power |
When the battery is fully charged, the measured power is ≤ 17.64W and the operating current is ≤ 2.1A When the battery is fully charged, the measured power is ≤ 35.28W and the operating current is ≤ 4.2A (Type B) |
|
|
Detection method |
Precision four wire method, simultaneous detection of 2 A/D channels |
|
|
range |
0.01 Ω~ 30.0k Ω; 0.01 Ω~ 300 Ω (Type B) |
|
|
Display rate |
0.0001Ω |
|
|
measurement accuracy |
0.1 Ω~ 30.0k Ω, △ ≤ 1% · Rx (Rx is the measured resistance value) 0.01Ω~0.0999Ω, △≤10%·Rx |
|
|
0.1 Ω~300 Ω, △ ≤ 1% · Rx (Rx is the measured resistance value) (Type B) 0.01 Ω~0.0999 Ω, △ ≤ 10% · Rx (Type B) |
||
|
test current |
HKCR3700 |
HKCR3700B |
|
30 Ω range: ≤ 2.1A; |
0.3 Ω range: ≤ 4.2A |
|
|
300 Ω range: ≤ 210mA; |
3 Ω range: ≤ 2.1A |
|
|
3kΩ档: ≤21mA; |
30 Ω range: ≤ 210mA |
|
|
30kΩ档: ≤2.1mA; |
300 Ω range: ≤ 21mA |
|
|
Wire length test |
L:≤999999m |
|
|
Standard wire length |
Standard wire length setting range: 1m to 30m |
|
|
test interface |
C1 current positive, C2 current negative, P1 voltage positive, P2 voltage negative |
|
|
measure time |
2 seconds/time |
|
|
data storage |
400 sets (data will not be lost in case of power failure or battery replacement) |
|
|
Alarm Settings |
Alarm threshold setting range: 1 Ω~30 Ω, 00 Ω does not activate the alarm function, and does not activate the alarm function every time it is turned on |
|
|
Alarm Alert |
When the test value exceeds the alarm set value, an alarm prompt of "beep beep beep beep beep" will appear |
|
|
Test instructions |
The blue Testing light flashes during the testing process |
|
|
Charging Indicator |
The indicator light on the charger lights up red when charging, and turns green when fully charged |
|
|
data retention |
Automatically maintain the display of the measured results after each test is completed |
|
|
Test line |
4 lines: 2 red and 2 black, each line is 5m long |
|
|
Backlight function |
Yes, suitable for dark places |
|
|
display mode |
LCD:128dots×64dots; 显示域: 44mm×27mm |
|
|
host size |
205mm×200mm×85mm |
|
|
Quality |
1.2kg |
|
|
Line voltage |
Should be avoided |
|
|
Overflow display |
Overscale overflow function: "OL" symbol display |
|
|
Low voltage indication |
When the battery voltage drops to 6.5V ± 0.1V, the low battery voltage symbol is displayed to remind timely charging. |
|
|
Working temperature and humidity |
-10℃~40℃; Below 80% RH |
|
|
Storage temperature and humidity |
-10℃~60℃; Below 70% RH |
|
|
charging port |
have |
|
|
RS232 interface |
Equipped with RS232 interface, software monitoring, data storage can be uploaded to the computer, saved and printed |
|
|
Voltage resistance |
AC 3700V/rms (between shell and screw) |
|
|
Suitable for safety regulations |
IEC61010-1, CAT Ⅲ 600V, Pollution Level 2, JJG724-1991 "Verification Regulations for DC Digital Ohmmeters", JJG166-1993 "Verification Regulations for DC Resistors", "DL/T967-2005 Verification Regulations for Loop Resistance Testers and DC Resistance Rapid Testers" |
|