HKSLQ-3-6000A three-phase high current generator
Wuhan Huadian Keyi Electric Co., Ltd. is a high-tech enterprise specializing in the research and development, production, sales, and service of power
Product details
Product Overview

The HKSLQ-3-6000A three-phase high current generator adopts imported high magnetic conductivity materials, with exquisite design, small size, strong resistance to electric power, and convenient use.

This series of high current generators is a necessary equipment for various industries that require high current places in electrical debugging, and is applied in power plants, substations, electrical manufacturing plants, scientific research, laboratories and other units.Applicable to frequencyCurrent load test and temperature rise test for 50HZ switches, current transformers, and other electrical equipment.

In addition, it belongs to the short-term or intermittent working system, which has the characteristics of small size, light weight, and good performance.

Features

Built in high configuration industrial computer

Adopting programmable controller SiemensAs the central processor, PLC performs real-time scanning of AC signals to achieve comprehensive monitoring and closed-loop control, and is designed with password setting management. Only personnel with corresponding operating permissions can perform certain functional operations.

ImportPC genuine color 10.0-inch large LCD touch screen operation

Adopting intelligent sensors that support fieldbus technology, data transmission is fully digitized. The display and operation unit adopts a touch sensitive color LCD screen, with a full Chinese menu and clear and intuitive interface, making operation simple and convenient. Testing does not require any external auxiliary equipment, fully automatic control, foolproof operation, fast, simple, and convenient

There are two testing methods: fully automated testing and manual testing

Just set a simple test current and time. Equipped with an automatic current stabilization system.

Fully automatic operation:

Just set the target current, no manual monitoring is required, only the testing, current, and step size need to be set, saving tedious labor such as manual voltage adjustment, manual recording, and curve drawing, reducing labor intensity, and improving work efficiency. After the work is completed, the data can be read to the computer for viewing.

Self protection mechanism:

The automatic alarm function for exceeding the limit value has reliable self-protection functions for overheating, overcurrent, overvoltage, and short circuit. The protection of the AC voltage regulating device should adopt dual protection of microcomputer automatic protection control and mechanical micro limit switch to ensure the normal operation of the constant current power supply and improve the safety and reliability of the product.

人性化界面

The software interface is user-friendly, with a fully Chinese operating interface. The control software has multiple practical functions such as data recording, storage of current and temperature waveforms, data management, reporting, printing, etc; All parameter settings are completed in the software. More intuitively analyze the relationship between current and temperature. Make all data and test analysis results clear at a glance. During the experiment, the target current is automatically tracked, the output current is automatically stabilized, and the three-phase current is automatically adjusted; After the experiment is completed, it will automatically return to zero position;

automatic adjustmentFunction:

Automatic adjustment of AC constant current source to meet the requirementsThe temperature rise test of the complete set of medium and low voltage switchgear (including control cabinets with multiple outputs such as GCK, MNS, etc.) according to GB 7251.1~GB 7251.5 standards should be able to achieve parallel operation of multiple constant current power sources during the temperature rise test with automatic adjustment of the AC constant current source (copies of proof materials for users using multiple constant current sources for parallel operation, such as GCK or MNS temperature rise test)

System:

Equipped with a three-phase automatic balancing system to ensure three-phase balanced output, the output current sampling adopts0.2S level transformer, adopting the latest power electronics technology, with strong anti-interference ability and high output accuracy, up to 0.5 level.

user-friendly design

Equipped with a precision adjustment menu, users can adjust the error value themselves. The program-controlled AC constant current power supply can achieve fully intelligent calibration, automatically generating multiple calibration coefficients within the adjustable range of the equipment to ensure the stability accuracy of the constant current power supply.

Software upgrade:

Test modules can be customized according to user requirements, and software can be upgraded for free for life

Built in power compensation system

Detailed specifications

model

HKSLQ-3-W6000A Three phase Temperature Rise High Current System

Maximum output current

AC single-phase 6000A 3 groups

circuit method

Special process electric voltage regulator

communication input

phase line

3Φ4W +G

voltage

380V ± 10%, 50Hz ± 2% three-phase four wire

input current

180A with compensation below 120A

output

phase line

3Φ4W

voltage

Phase voltage 0-10V, line voltage 17.732V

current

AC0-6300A continuously adjustable, stepless speed regulation mode;

It can output three phases simultaneously, single-phase, or phase separated;

There are two modes of output: manual mode and automatic mode.

Rated capacity

200kVA

current stability accuracy

Output current ≤± 0.5%

output terminal

terminal block

protect

Electronic circuits quickly detect overvoltage, overcurrent, overtemperature, phase loss, automatic tripping protection and alarm devices, with zero voltage and zero current in non test state

precision

Source effect

≤ 0.3% rated value

Time drift

≤ 1% rated value

temperature drift

≤ 0.04% rated value/℃

Load effect

≤ 1% rated value (only the rate of change in output voltage caused by the change in output current from zero to rated value)

ripple voltage

≤ 1% rated value+10mV

other

Line adjustment rate:

0.1%

Load adjustment rate:

0.1%

display

And setting

Voltage meter display

True color LCD and digital display instrument (display accuracy: 0.1V, display error: ≤ 0.2% ± 1 word)

Current meter display

True color LCD and digital display instrument(6Digital display, display accuracy of 0.1A, display error: ≤ 0.2% ± 1 word)

Adjust settings

Current (touch screen setting)

system

overall efficiency

≥90%

Voltage resistant insulation impedance

AC 1800V for 1 minute, 20 megaohms

cooling system

Forced fan cooling

noise

< 60dB (1mm in front of the machine)

Transformer accuracy

0.2S level

Protection level

IP20

work

environment

working method

Long term temperature rise experiment

temperature

-10℃-50℃

humidity

0-90% (non condensing state)

altitude

Below 1500m

appearance

structure

Integrated temperature rise

size

待定

weight

about3ton

busbar

Output calculated at 1-1.2 currents per square, later

Temperature Inspection

temperature measurement point

8 channels, capable of measuring 8 monitoring points. If temperature measurement points need to be added, they can be upgraded and raised

K-Type

To improve accuracy, PT1000 is used within 5 meters