The HKSLQ-3-6000A three-phase high current generator adopts imported high magnetic conductivity materials, with exquisite design, small size, strong resistance to electric power, and convenient use.
This series of high current generators is a necessary equipment for various industries that require high current places in electrical debugging, and is applied in power plants, substations, electrical manufacturing plants, scientific research, laboratories and other units.Applicable to frequencyCurrent load test and temperature rise test for 50HZ switches, current transformers, and other electrical equipment.
In addition, it belongs to the short-term or intermittent working system, which has the characteristics of small size, light weight, and good performance.
①Built in high configuration industrial computer:
Adopting programmable controller SiemensAs the central processor, PLC performs real-time scanning of AC signals to achieve comprehensive monitoring and closed-loop control, and is designed with password setting management. Only personnel with corresponding operating permissions can perform certain functional operations.
②ImportPC genuine color 10.0-inch large LCD touch screen operation:
Adopting intelligent sensors that support fieldbus technology, data transmission is fully digitized. The display and operation unit adopts a touch sensitive color LCD screen, with a full Chinese menu and clear and intuitive interface, making operation simple and convenient. Testing does not require any external auxiliary equipment, fully automatic control, foolproof operation, fast, simple, and convenient
③There are two testing methods: fully automated testing and manual testing:
Just set a simple test current and time. Equipped with an automatic current stabilization system.
④Fully automatic operation:
Just set the target current, no manual monitoring is required, only the testing, current, and step size need to be set, saving tedious labor such as manual voltage adjustment, manual recording, and curve drawing, reducing labor intensity, and improving work efficiency. After the work is completed, the data can be read to the computer for viewing.
⑤Self protection mechanism:
The automatic alarm function for exceeding the limit value has reliable self-protection functions for overheating, overcurrent, overvoltage, and short circuit. The protection of the AC voltage regulating device should adopt dual protection of microcomputer automatic protection control and mechanical micro limit switch to ensure the normal operation of the constant current power supply and improve the safety and reliability of the product.
⑥人性化界面:
The software interface is user-friendly, with a fully Chinese operating interface. The control software has multiple practical functions such as data recording, storage of current and temperature waveforms, data management, reporting, printing, etc; All parameter settings are completed in the software. More intuitively analyze the relationship between current and temperature. Make all data and test analysis results clear at a glance. During the experiment, the target current is automatically tracked, the output current is automatically stabilized, and the three-phase current is automatically adjusted; After the experiment is completed, it will automatically return to zero position;
⑦automatic adjustmentFunction:
Automatic adjustment of AC constant current source to meet the requirementsThe temperature rise test of the complete set of medium and low voltage switchgear (including control cabinets with multiple outputs such as GCK, MNS, etc.) according to GB 7251.1~GB 7251.5 standards should be able to achieve parallel operation of multiple constant current power sources during the temperature rise test with automatic adjustment of the AC constant current source (copies of proof materials for users using multiple constant current sources for parallel operation, such as GCK or MNS temperature rise test)
⑧System:
Equipped with a three-phase automatic balancing system to ensure three-phase balanced output, the output current sampling adopts0.2S level transformer, adopting the latest power electronics technology, with strong anti-interference ability and high output accuracy, up to 0.5 level.
⑨user-friendly design
Equipped with a precision adjustment menu, users can adjust the error value themselves. The program-controlled AC constant current power supply can achieve fully intelligent calibration, automatically generating multiple calibration coefficients within the adjustable range of the equipment to ensure the stability accuracy of the constant current power supply.
⑩Software upgrade:
Test modules can be customized according to user requirements, and software can be upgraded for free for life
⑪Built in power compensation system
|
model |
HKSLQ-3-W6000A Three phase Temperature Rise High Current System |
|
|
Maximum output current |
AC single-phase 6000A 3 groups |
|
|
circuit method |
Special process electric voltage regulator |
|
|
communication input |
phase line |
3Φ4W +G |
|
voltage |
380V ± 10%, 50Hz ± 2% three-phase four wire |
|
|
input current |
180A with compensation below 120A |
|
|
output |
phase line |
3Φ4W |
|
voltage |
Phase voltage 0-10V, line voltage 17.732V |
|
|
current |
AC0-6300A continuously adjustable, stepless speed regulation mode; It can output three phases simultaneously, single-phase, or phase separated; There are two modes of output: manual mode and automatic mode. |
|
|
Rated capacity |
200kVA |
|
|
current stability accuracy |
Output current ≤± 0.5% |
|
|
output terminal |
terminal block |
|
|
protect |
Electronic circuits quickly detect overvoltage, overcurrent, overtemperature, phase loss, automatic tripping protection and alarm devices, with zero voltage and zero current in non test state |
|
|
precision |
Source effect |
≤ 0.3% rated value |
|
Time drift |
≤ 1% rated value |
|
|
temperature drift |
≤ 0.04% rated value/℃ |
|
|
Load effect |
≤ 1% rated value (only the rate of change in output voltage caused by the change in output current from zero to rated value) |
|
|
ripple voltage |
≤ 1% rated value+10mV |
|
|
other |
Line adjustment rate: |
0.1% |
|
Load adjustment rate: |
0.1% |
|
|
display And setting |
Voltage meter display |
True color LCD and digital display instrument (display accuracy: 0.1V, display error: ≤ 0.2% ± 1 word) |
|
Current meter display |
True color LCD and digital display instrument(6Digital display, display accuracy of 0.1A, display error: ≤ 0.2% ± 1 word) |
|
|
Adjust settings |
Current (touch screen setting) |
|
|
system |
overall efficiency |
≥90% |
|
Voltage resistant insulation impedance |
AC 1800V for 1 minute, 20 megaohms |
|
|
cooling system |
Forced fan cooling |
|
|
noise |
< 60dB (1mm in front of the machine) |
|
|
Transformer accuracy |
0.2S level |
|
|
Protection level |
IP20 |
|
|
work environment |
working method |
Long term temperature rise experiment |
|
temperature |
-10℃-50℃ |
|
|
humidity |
0-90% (non condensing state) |
|
|
altitude |
Below 1500m |
|
|
appearance |
structure |
Integrated temperature rise |
|
|
size |
待定 |
|
|
weight |
about3ton |
|
|
busbar |
Output calculated at 1-1.2 currents per square, later |
|
Temperature Inspection |
temperature measurement point |
8 channels, capable of measuring 8 monitoring points. If temperature measurement points need to be added, they can be upgraded and raised |
|
K-Type |
To improve accuracy, PT1000 is used within 5 meters |
|